Technical Specifications
| MODEL | ST10K | ||
|---|---|---|---|
| PHASE | 3-phase in / 3-phase out | ||
| MAXIMUM PV INPUT POWER | 14850 W | ||
| RATED OUTPUT POWER | 10000 W | ||
| MAXIMUM CHARGING POWER | 9600 W | ||
| GRID-TIE OPERATION | |||
| PV INPUT (DC) | Nominal DC Voltage / Maximum DC Voltage | 720 VDC / 900 VDC | |
| Start-up Voltage / Initial Feeding Voltage | 320 VDC / 350 VDC | ||
| MPP Voltage Range | 400 VDC ~ 800 VDC | ||
| Number of MPP Trackers / Maximum Input Current | 2 / 2 x 18.6A | ||
| GRID OUTPUT (AC) | Nominal Output Voltage | 230 VAC (P-N) / 400 VAC (P-P) | |
| Output Voltage Range | 184 – 265 VAC* per phase | ||
| Nominal Output Current | 14.5A per phase | ||
| Power Factor | > 0.99 | ||
| EFFICIENCY | Maximum Conversion Efficiency (DC/AC) | 96% | |
| European Efficiency@ Vnominal | 95% | ||
| OFF-GRID OPERATION | |||
| AC INPUT | AC Start-up Voltage/Auto Restart Voltage | 120 – 140 VAC per phase / 180 VAC per phase | |
| Acceptable Input Voltage Range | 170 – 280 VAC per phase | ||
| Maximum AC Input Current | 40 A | ||
| PV INPUT (DC) | Maximum DC Voltage | 900 VDC | |
| MPP Voltage Range | 400 VDC ~ 800 VDC | ||
| Number of MPP Trackers / Maximum Input Current | 2 / 2 x 18.6A | ||
| BATTERY MODE OUTPUT (AC) | Nominal Output Voltage | 230 VAC (P-N) / 400 VAC (P-P) | |
| Output Waveform | Pure Sinewave | ||
| Efficiency (DC to AC) | 91% | ||
| HYBRID OPERATION | |||
| PV INPUT (DC) | Nominal DC Voltage / Maximum DC Voltage | 720 VDC / 900 VDC | |
| Start-up Voltage / Initial Feeding Voltage | 320 VDC / 350 VDC | ||
| MPP Voltage Range | 400 VDC ~ 800 VDC | ||
| Number of MPP Trackers / Maximum Input Current | 2 / 2 x 18.6A | ||
| GRID OUTPUT (AC) | Nominal Output Voltage | 230 VAC (P-N) / 400 VAC (P-P) | |
| Output Voltage Range | 184 – 264.5 VAC* per phase | ||
| Nominal Output Current | 14.5 A per phase | ||
| AC INPUT | AC Start-up Voltage / Auto Restart Voltage | 120 – 140 VAC per phase / 180 VAC per phase | |
| Acceptable Input Voltage Range | 170 – 280 VAC per phase | ||
| Maximum AC Input Current | 40 A | ||
| BATTERY MODE OUTPUT (AC) | Nominal Output Voltage | 230 VAC (P-N) / 400 VAC (P-P) | |
| Efficiency (DC to AC) | 91% | ||
| BATTERY & CHARGER | Nominal DC Voltage | 48 VDC | |
| Maximum Charging Current Adjustable | Default 60A, 10A – 200A | ||
| GENERAL | |||
| PHYSICAL | Dimension, D X W X H (mm) | 167.5 x 500 x 622 | |
| Net Weight (kgs) | 45 | ||
| INTERFACE | Communication Port | RS-232/USB and CAN Interface | |
| Intelligent Slot | Optional SNMP, Modbus and AS-400 cards available | ||
| ENVIRONMENT | Humidity | 0 ~ 90% RH (No condensing) | |
| Operating Temperature | -10 to 55°C | ||